Swing Check valves are available in a variety of connection types including compression, slip and slip union. How do you know what connection you need and how do you install it?
In this blog, we will go over when a slip connection valve is used, the options you have when picking your slip connection valve, and the steps needed to properly install a slip connection valve in a sump pump, effluent or sewage system.
A slip connection is used when joining PVC or ABS plastic piping. A solvent weld connection is required
Before installing you must design the system piping layout and determine which valve is best for your sump pump, effluent or sewage system.
PVC Swing Check Valves provide reliable back flow protection, along with a designed angle seat to minimizes flow reversal, and potentially damaging hydraulic shock.
PVC Ball/Swing Combination Valves feature both an in-line shut off and back flow prevention which makes it a compact option, along with a designed angle seat to minimizes flow reversal, and potentially damaging hydraulic shock.
Both of the above valves are available in a standard or quiet option.
STEP BY STEP SLIP INSTALLATION PROCESS
Step 1 - Design the system piping layout and cut piping to the appropriate length.
The proper location for the check valve is close to the floor level to both minimize the volume of water which drains back at the end of each pumping cycle, as well as to have the valve in a convenient location for easy inspection and servicing or replacement of the valve.
Step 2 - Clean both pipe-ends and slip sockets of the valve. All parts that are to be solvent weld cemented must be clean of all foreign materials.
Step 3 - Mark both the inlet and discharge pipes (refer to installation instructions for appropriate length).
Step 4 - Locate the flow direction arrow on the valve body to ensure proper orientation of the valve from the pump.
Best practice is to install valves in the VERTICAL position when pumping solid free liquids.
When pumping solids / semi-solids valve must be installed HORIZONTALLY (up to 45° angle acceptable, see #1). Extra care must be taken to ensure the flow arrow points away from the pump and the check valve body is oriented as per the marking on the valve body “HORIZONTAL USE THIS SIDE UP”. Failure to position the swing check valve with the hinge of the flapper in the top center position will result in the valve not functioning properly.
Step 5 - Wear gloves, solvent weld the pipe from the pump into the inlet connection of the valve, make sure the pipe is fully inserted into the slip socket.
Step 6 - Solvent weld the outlet connection, make sure the pipe is fully inserted into the slip socket.
Step 7 - Let connections cure.
Step 8 - Properly support and restrain discharge piping, the pipeline must be restrained to prevent lateral movement by end blocking at direction changes and at any reduction in pipe size.
Step 9 - TEST your connection to ensure a leak-free seal.
Always refer to local building / plumbing codes to ensure the installation meets all regulations.
Caution: If you are not comfortable installing these yourself, make sure that you get a certified Plumber to do it for you. If these products are not installed correctly, it may cause flooding and other issues.
For more information, check out our Ultimate Sump and Sewage Check Valve overview page.